The decision: addressable or conventional
A conventional panel knows a zone. An addressable panel knows a device. On a single-floor workshop with four zones, a responding officer can walk a zone in under a minute and conventional detection remains defensible. In a hospital wing, a hotel floor plate or an assembly building, walking a zone means walking a corridor with fifty doors while the alarm is sounding, and the difference between zone-level and device-level identification is the difference between a controlled investigation and an evacuation.
Read the rest of this section as an engineering judgement, not a compliance test. We previously stated a building height in Assam above which addressable detection is required; that threshold was attributed to NBC 2016 Part 4 and IS 2189, our own primary-source review of those documents did not support it, and it has been withdrawn. We therefore do not state a height at which conventional detection stops being permissible, and nothing on this page should be read as ruling a conventional proposal non-compliant. The statutory position sits with the Assam Fire and Emergency Services rule and the authority having jurisdiction — settle it with them at design-stage submission, and treat the judgement below as how we would choose between the two technologies once that is known.
The second half of the decision is the cause-and-effect matrix, and it is the half most briefs omit. Detection tells you something is burning; cause-and-effect decides what the building does about it — which air-handling units stop, which dampers close, which lifts return to the ground floor and release, which doors release for egress and which stay closed for compartmentation, what the public-address system says and in what order of floors. A conventional panel can drive a simple matrix. Anything with staged evacuation, lift homing or smoke-control interlocks needs device-level addressing to express the logic at all.
Retrofit changes the arithmetic. Where an existing building already has sound conventional loop wiring in serviceable containment, a hybrid approach — addressable panel, conventional zone modules on the retained legacy wiring, full addressing on new-build areas — is often the honest answer rather than tearing out working cable to satisfy a preference.