Skip to content
TechnoGuru — Think Technology, Think TechnoGuru

Energy Readiness · Healthcare

100,000 sq ft 24×7 hospital: ~529,000 kWh/yr in play

Problem. A hospital engineering team scoping a BMS and lighting-controls programme on a 100,000 sq ft, 24×7 building needs an early sense of the annual electricity a coordinated energy pass could address. With continuous clinical operation the baseline is large, so a defensible first-pass number matters before any detailed measurement.

Answer. At a hospital energy-performance index of 340 kWh/m²/yr across ~9,290 m², this configuration models a baseline near 3.16 million kWh/yr, of which about 16.75 percent — close to 529,000 kWh/yr — is addressable through HVAC, lighting and scheduling measures. That band carries roughly 376 tonnes of CO₂ a year at the CEA grid factor of 0.71 kg/kWh.

02 / In depth

How this preset reads — the engineering view.

The model applies a BEE-style EPI to floor area and an operating-hours factor. A 24×7 hospital sits at a midpoint EPI of 340 kWh/m²/yr — four times a typical office — with roughly 50 percent HVAC and 15 percent lighting. The addressable band uses the same ASHRAE 90.1 / BEE midpoints (16 percent of HVAC, 35 percent of lighting, 3.5 percent of total), which for this heavier, less lighting-weighted mix resolve to about 16.75 percent.

The 100,000 sq ft input converts to ~9,290 m² (÷ 10.7639). Multiplying 340 × 9,290 gives a baseline near 3.16 million kWh/yr; 16.75 percent of that is close to 529,000 kWh/yr addressable, carrying roughly 376 tonnes of CO₂ a year. Note the contrast with the office preset: the far higher EPI and larger area produce a much larger absolute kWh headline, yet at a slightly lower percentage because lighting — the highest-yield category — is a smaller share of a hospital's load.

Raising floor area or the operating-hours factor increases the absolute kWh in play monotonically, since both enlarge the baseline. The percentage is fixed by the hospital use-mix and moves only if that mix changes — which is why a bigger hospital shows a bigger kWh headline at the same ~16.75 percent. Separate the two readings: the kWh is the area-and-hours story, the percentage is the use-mix story.

For a hospital, energy is only part of the case. This tool models addressable energy alone — it does not model clinical resilience, redundancy, emergency-power continuity, infection-control airflow or statutory compliance, all of which usually drive a hospital BMS more than energy does. It also excludes the installed plant, real occupancy and tariff detail, so treat the output as a screening figure that frames the energy conversation, not the whole business case.

What this preset deliberately does not solve

  • Screening estimate from EPI midpoints — not a metered saving or an audit result.
  • Models energy only — not resilience, redundancy, emergency power or compliance, which usually lead a hospital BMS.
  • The percentage reflects the hospital use-mix; the kWh headline scales with area and 24×7 hours.

How this preset differs from its siblings

The sibling office preset models a much lower EPI (85 vs 340 kWh/m²/yr) over a smaller, 12-hour footprint, so it shows a smaller absolute kWh saving at a slightly higher percentage — lighting is a larger share of an office load. Use this hospital preset for a 24×7 clinical building where continuous operation sets a very large baseline and BMS scope extends well beyond energy; use the office preset for a daytime commercial retrofit where lighting and HVAC are the primary levers.

03 / Hydrated calculator

Try the configuration — live.

The calculator below is preloaded with this preset’s state. Adjust any input — your URL stays shareable.

— Energy · BMS & lighting retrofit · BEE / ECBC / ASHRAE 90.1 / CEA

The energy case, in plain numbers.

Use-type Energy Performance Indices from BEE ECBC 2017 + GRIHA v3, BMS savings calibrated to ASHRAE 90.1 retrofit studies, CO₂ tied to CEA grid emission factor. Defensible at board level; pricing follows a written estimate after review.

Energy readiness · Hospital / healthcare (24-hr)

5,29,083 kWh / yr saving potential

≈ 17% of an estimated 31,58,706 kWh / yr baseline — at 340 kWh / m² · yr energy intensity. The saving scales with floor area and operating hours; the percentage reflects the building use-mix. Indicative energy planning, not a quotation.

Indicative

Annual energy (baseline)

31,58,706 kWh

at 340 kWh / m² · yr

Energy saving potential

5,29,083 kWh / yr

≈ 17% of consumption

CO₂ avoided

376 t / yr

CEA grid · 0.71 kg / kWh

  • BMS / HVAC saving2,52,697 kWh
  • Lighting retrofit1,65,832 kWh
  • Tariff / PF optimisation1,10,555 kWh
  • CO₂ avoided376 t / yr
Assumptions driving this recommendation↓ expand
EPI band source
BEE ECBC 2017 · GRIHA v3
EPI applied
340 kWh / m² · yr
HVAC share
50%
Lighting share
15%
BMS savings (ASHRAE 90.1)
16% of HVAC load
LED + harvesting
35% of lighting load
Tariff / PF
3.5% of total load
CO₂ factor (CEA grid)
0.71 kg / kWh
Standards cited
BEE ECBC · GRIHA · ASHRAE 90.1 · CEA

Engineering caveats

  • HVAC dominates this use-type's energy — the controls layer (BMS sequencing, schedules, setpoint discipline) carries most of the achievable saving; metering and a baseline survey calibrate the real figure.

Operationally sensible ecosystem

Brands grouped by engineering role — not random logos.

BMS platform

BACnet / Niagara orchestration

  • Honeywell EBIMid-enterprise BMS
  • Delta enteliWEBWeb-based mid-enterprise

Lighting & control

Backbone bus, keypads, drivers, dimming

  • Lutron HomeWorksReference residential bus
  • KNX (ABB / Gira)European hardwired standard
  • RakoBritish keypad lineage

UPS / power conditioning

Single + 3-phase + transfer

  • APC Symmetra LXModular 3-phase mid
  • Vertiv Liebert APMModular 3-phase mid

Indicative — modelled against BEE ECBC 2017 EPI bands and ASHRAE 90.1 retrofit savings ratios. A site audit calibrates against actual consumption, building envelope, weather profile and existing condition. Pricing and commercial payback follow a written estimate after technical review.

A planning link that reopens this exact configuration — not a quote.

Pricing · written estimate after review

Need a price for this scope?

Share your drawings, BOQ or project brief on WhatsApp/call +91 88110 34444 or email info@technoguru.in for a written estimate after review. Pricing depends on drawings, site conditions, system scope, brand selection, cabling stage, integration depth, commissioning, logistics, GST, approvals and support expectations — so we prepare it per project after a technical review rather than publishing standard rates.

Size battery storage for the load

Energy readiness report

Print-styled energy brief, ready to circulate.

Opens in a new tab — save as PDF via your browser, or email it to yourself via the gate below. Energy figures only; pricing follows a written estimate after review.

Or email the report

We'll email you a PDF of the energy readiness report and (optionally) a project lead will follow up if the brief is a fit. Two-day reply, no sales pipeline.

DPDPA-compliant · we never sell data · see data protection

Save or share this planning tool

Send it to your consultant or architect.

· Next

Brief us on the project — with this configuration.

Presets are a typology starting point. The brief wizard captures the room geometry, programme and constraints we need to translate this configuration into a real design.